Peabody releases initial “Learnings” from 2018 North Goonyella incident.

Peabody Coal has released initial lessons from the North Goonyella mine fire of September, 2018.

Findings are based on the company’s review of the events surrounding the fire. They include the mine general manager’s investigation report, prepared in accordance with Section 201 of the Queensland Coal Mining Safety and Health Act of 1999.

The underground coking coal mine – teasingly called “the Goon Show” – is located 160km west of Mackay and exports via Dalrymple Bay coal terminal. Before the crippling fire, the mine produced 3 millions tons (sic) of coal in 2017 and employed over 200 people.

Critics – including AFR’s Matthew Stevens (paywalled) and Australasian Mine Safety Journal’s John Ninness – spoke harshly of both the company and the Queensland government for extreme tardiness in admitting there was an incident, or then that “smoke really did mean fire.”

On 28 September 2018, Queensland Mines Inspectorate issued a bulletin detailing a potential mine fire:

On 1 September 2018, Peabody Energy, operator of North Goonyella coal mine made a safety-based decision to remove all personnel from the underground mine. This was in response to elevated gas readings at the location of the longwall block that it had recently been mining.

Between 2 and 26 September Peabody made attempts to manage suspected heating of coal, to enable re-entry to the mine and continue mining operations.

On 27 September, smoke was observed rising from the main exhaust fan. This indicates combustion of coal underground.

As at 28 September, smoke continues to be emitted from the underground workings.

Peabody had an experienced team dealing with heating events, with advisors such as Dr David Cliff from UoQ, and also a sophisticated tube bundle gas analysis system.

North Bowen Basin mines were extensively studied regarding “inertisation” over twenty years ago.

Peabody Report

When the serious incident at North Goonyella occurred, Peabody committed to sharing learnings for the benefit of our operations, our stakeholders and others in the industry," said Peabody President and Chief Executive Officer Glenn Kellow.

We believe that the beginning of the planned reventilation and re-entry activities warrant a sharing of our initial learnings at this point. We are taking multiple actions to integrate these learnings into our practices at North Goonyella and our other operations, where appropriate.

The goal here is clear, to reduce the risk of such an event reoccurring at North Goonyella or any of our other mines in the future."

In early September, high gas levels caused the evacuation of personnel at North Goonyella during a planned longwall move from the 9 North panel to the 10 North panel. Subsequently, elevated carbon monoxide detected from within the mine indicated oxidation of coal, which can occur when coal is exposed to oxygen for an extended time period. Over a number of weeks, the company worked together with industry experts, and in consultation with the Queensland Mines Inspectorate (QMI), to take extensive steps to treat the oxidation from the mine surface. Actions were ultimately unsuccessful, and a fire occurred in late September.

The company’s review of the incident concluded that areas of the mine demonstrated both elevated methane levels and elevated carbon monoxide levels following completion of coal production in the 9 North panel. During the longwall move sequence, a change in gas management focus to reduce elevated methane levels in the 9 North panel, including changes to the mine’s ventilation system to increase airflow, inadvertently intensified the oxidation of coal that was likely causing elevated carbon monoxide levels.

Despite sustained efforts to manage the oxidation from the mine surface, including use of nitrogen to create an inert environment within the 9 North panel goaf (the mined-out area in the panel), the oxidation accelerated into a spontaneous combustion event that eventually resulted in the fire.

Safety remains Peabody’s number-one priority and its first value. As a result of the actions taken to evacuate personnel in advance of the fire and other controls in place, the incident did not result in injury to any person. Throughout the incident Peabody’s incident management team worked alongside the QMI and industry experts to ensure it utilized the best people and resources. Peabody continues to cooperate fully with the QMI as it undertakes its own independent investigation into the incident.

President, Australian Operations, George Schuller said,

"While this was a highly unusual combination of events, Peabody is making changes in systems, processes and training, where warranted, to put into place the improvements needed to successfully move forward from this incident. For example, we have already begun installing remote control ventilation systems at mine entrances."

It is the company’s intent that longwall production at North Goonyella will not recommence until all necessary modifications are undertaken. Peabody’s base case that targets limited continuous-miner volumes in 2019 with longwall production beginning to ramp up in early 2020 remains unchanged with approximately 2 million tons of sales from North Goonyella in 2020. Peabody continues to progress the execution of the multi-phased reventilation and re-entry of the mine in consultation with the QMI.

I want to thank Peabody employees, the union, customers, neighboring mines, the community of Moranbah, the Inspectorate and countless others who have helped out during this challenging time," said Schuller.

We will be contacting other coal companies and industry bodies to further share learnings in coming months to strengthen the body of knowledge around underground mine ventilation and fire prevention."

Peabody discussion below warns “it is not possible to predict or identify all factors within ‘forward-looking statements’ and any such list is not a complete set of all potential risks or uncertainties.”

Discussion of Key Initial Learnings

As a result of Peabody’s comprehensive review, the company has developed initial learnings and steps to improve the longwall move process and other mining activities.

a) Peabody will review ventilation controls and design used during the
longwall "take-off" process to minimize the amount of air that enters
the longwall panel goaf and interacts with exposed coal remaining
within the goaf. Ventilation controls that were put into place in
advance of the longwall take-off process may have permitted higher-than-
expected volumes of ventilation air to enter the goaf during the
longwall take-off process, resulting in oxidation. Gas management and
ventilation changes were made in and around the 9 North panel tailgate
area in response to elevated levels of methane, which inadvertently
intensified the oxidation.

b) Evaluate decision-making processes to address the challenges of
remotely managing an underground incident solely from the surface,
which can lead to unclear or ambiguous results. For instance, as the
incident approached late September and treatment of the oxidation event
escalated, including injection of nitrogen from the mine surface into
the 9 North panel goaf, fluctuating gas readings led North Goonyella
mine personnel and expert third-parties to believe that the treatment
plan was likely working due to a purging of gases from the goaf.

c) Peabody also believes that the system used to monitor and analyze
available mine gas data can be improved and better coordinated to
identify early stages of oxidation events. Additional training to the
appropriate mine personnel will be implemented to recognize fire gas
indicators, gas management and spontaneous combustion, and provide an
understanding of a mine’s ventilation history, with focus on
identifying ventilation trends and key indicators of oxidation and
developing heating for longwall mines.

d) Peabody will modify the longwall removal planning process to reduce the
number of days to complete the longwall take-off process to allow for
earlier commencement of final sealing, incorporating additional
contingency planning in the event the target cannot be achieved. The
amount of time the North Goonyella mine’s 9 North panel was idle
increased the propensity for oxidation to occur in the longwall panel
goaf. Peabody will consider additional contingency measures, including
installation of pre-drilled holes at the appropriate locations
immediately behind the longwall chock line to allow oxygen inhibitors
to be injected when longwall advance stops to mitigate against
oxidation.

e) Peabody will improve the Sealing Management Plan to provide greater
clarity around the required steps for sealing the longwall panel
(particularly in relation to how these steps interact and relate to the
longwall move and re-installation plan). The improved plan will
provide for the allocation of resources to ensure the Sealing
Management Plan is followed as described. Peabody will also provide
additional training for underground personnel prior to sealing
operations commencing.

f) Peabody will hone its system for the management of Trigger Actions
Response Plans (TARPs) to provide clearly defined trigger points, clear
explanations of actions to be taken if trigger levels are reached, and
improved methods, training and communications involving changing
TARPs. Application and progression of TARPs during the longwall take-
off process varied from that set out in the Sealing Management Plan,
and communication of TARPs was found to be inconsistent. TARPs
describe actions that must be taken by mine personnel in response to
observation of certain conditions or triggers (e.g. gas levels) that
deviate from normal. TARPs should clearly define their applicability
and the required action items when trigger points are reached.

g) Peabody will review the Principal Hazard Management Plan (PHMP) for
Spontaneous Combustion and Emergency Response around the provision of
clear and concise guidance in relation to gas readings. The company
will also implement a regime for reviewing the PHMP at established
intervals and updating as required.

h) Within the Site Incident Management Team (SIMT), Peabody will appoint
an independent facilitator whose role will be to assist the SIMT in the
decision-making process (rather than the technical aspects of SIMT
decisions). The SIMT was comprised primarily of North Goonyella mine
management personnel, though various other parties also provided input
into the SIMT’s decision making process. At times, it was challenging
for the SIMT to coordinate and address differing viewpoints from
multiple stakeholders. Although these outside parties each play
critical roles in responding to a mine emergency, the varied viewpoints
need to be effectively managed and facilitated during an incident.

i) Peabody is taking action to install quickly closable remote ventilation
control devices at each mine drift as we progress through the
reventilation process. In addition, Peabody will evaluate options to
remotely isolate portions of the longwall panel to provide an option to
quickly close these devices after all personnel have been evacuated
from the panel. Peabody’s ability to quickly seal the panel to
extinguish the oxidation event before it developed into a fire was
impaired once the mine was evacuated and exclusion zones were put in
place. Once an oxidation event develops into a spontaneous combustion
event, it is difficult to extinguish from the mine surface. The
smaller the area of the mine that is sealed from the source of
combustion, the less oxygen is available to support it and the quicker
it begins to cool, which should facilitate expeditious recovery. These
types of devices could be closed by personnel as part of an evacuation
sequence, or through remote means. Emergency seals, which can be
installed at chute and gate roads at longwall panels, will also be
considered as part of an emergency sealing process.